按照欧洲规范 EN 1993-1-1 计算变截面钢结构柱

技术文章

该技术报告引用的实例为专业文献 [1] "欧洲规范3条文说明" 的实例 IV.10。对于截面按照线性变化的钢结构柱或其他杆件需要按照规范给定的特殊方法验算其承载力(截面强度和稳定性验算)。由于构件的截面为变截面形式,需要按照规范 6.3.4 条所规定方法验算其稳定性(主平面内),或者按照二阶理论验算。

System

Cross-Section: IS 220/300/15/25/0 (column base), IS 620/300/15/25/0 (column head)
Material: S 355 (DIN EN 1993-1-1)
Column height: 6.0 m
On the tension side of the cross-section is a continuous support in the Y-direction (lateral rotation axis).

Loads

Design loads:
NEd = 1,500 kN
MEd = 600 kNm

Figure 01 - Structural System

Cross-Section Classification

With the existing design loads, the cross-section does not reach the ultimate limit state curve. Therefore, the internal forces must be increased up to the ultimate state.
For this, there are two options:
  1. Linearly increase all internal forces until the ultimate state is reached (see Figure 02 left, the second option (default) in Details)
  2. Increase only MEd to reach the ultimate state (see Figure 02 right, the first option in Details)

Figure 02 - Classification of Cross-Sections

Both options and methods lead to very different results, from a maximum elastic design in the top third to a completely possible plastic design ration of the cross-section over the entire column height.

In the present stability failure, no increment of the axial force arises, but only an increment of the moments due to deformations and the second-order analysis. Therefore, the second option is selected.

Minimum Amplifier αult,k

In this case, the cross-section design ration is determined by using the linear plastic interaction (see [2] Eq. 6.2). This must be activated in Details, since RF-/STEEL EC3 performs the design for the cross-sections of Class 1 or 2 according to Eq. 6.31 or 6.41 of [2] by default.

In compliance with Section 6.3.4. (2), it may be necessary to calculate the minimum load amplifier αult,k to reach the characteristic resistance in the main plane with all effects of imperfections and the second-order analysis.

The check, as far as deformations affect the internal forces, is determined according to Equation 5.1 in [2]:
$$\alpha_{cr}\;=\;\frac{N_{cr}}{N_{Ed}}\;>\;10$$

In this case, αcr should be determined by RF-/STEEL EC3 and RF-/STEEL Warping Torsion. The best way is to generate a separate module case and define intermediate lateral restraints for the set of members in order to enforce the first mode shape with 'buckling in the major axis direction'.

Figure 03 - First Mode Shape

αcr = 18.90 >10

The cross-section design ratio and thus the minimum load amplifier αult,k can be calculated with the internal forces according to the linear static analysis. The following ratios and factors then arise along the member length.

Figure 04 - Minimum Amplifiers and Design Ratios

Slenderness of Structural Component and Reduction Factor χop

Determination of the reduction factor χop requires the slenderness ratio λop to take into account flexural buckling or lateral-torsional buckling. This is calculated according to Equation 6.64 of [2]:
$$\lambda_{op}\;=\;\sqrt{\frac{\alpha_{ult,k}}{\alpha_{cr,op}}}$$
where
αult,k = see above
αcr,op is the minimum amplifier to reach the elastic critical load with regards to lateral or lateral torsional buckling.

During the design according to 6.3.4, the RF-/STEEL EC3 solver determines the minimum load amplifier to reach the elastic critical load of the structural component with regards to lateral or lateral torsional buckling. Properties of the underlying structural system are specified in Window 1.4 and 1.7 as follows.

Figure 05 - Properties of Structural System

Based on the reference literature, elastic warping restraints were waived, although they would be justified due to the base plate and also the present restraint on the column head. The calculation result is:

Figure 06 - alpha,cr,op

Thus, it is possible to determine the slenderness of the structural component according to [2], Section 6.3.4:
$$\lambda_{op}\;=\;\sqrt{\frac{2.097}{3.23}}\;=\;0.805$$

The buckling curve can be selected in compliance with National Annex (NDP to 6.3.4 (1)) according to Table NA.4:
Buckling, Table 6.2 (welded I-section, tf < 40 mm, buckling in y): BC 'c'
Lateral-torsional buckling, Table 6.4 (h / b = 2.07 > 2): BC 'd'

In the case of combined effects, the following minimum load amplifier should be used:
χop,z = 0.659 (Eq. 6.49)
χop,LT = 0.684 (Eq. 6.57)
χop = min {χop,LT; χop,z}
χop = 0.659

Component Design

The actual design is now performed according to [2], 6.3.4 (2), Equation 6.63:
$$\frac{\chi_{op}\;\cdot\;\alpha_{ult,k}}{\gamma_{M,1}}\;>\;1.0$$
Adjustment of the equation in terms of the design ratio:
$$\frac{\gamma_{M,1}}{\chi_{op}\;\cdot\;\alpha_{ult,k}}\;<\;1.0$$
$$\frac{1.1}{0.659\;\cdot\;2.097}\;=\;0.80\;<\;1.0$$

Reference

[1]  Feldmann, M.; Kuhlmann, U.; Lindner, J.; Müller, C.; Stroetmann, R. (2014). Eurocode 3 Bemessung und Konstruktion von Stahlbauten - Band 1: Allgemeine Regeln und Hochbau. DIN EN 1993-1-1 mit Nationalem Anhang. Kommentar und Beispiele. Berlin: Beuth.
[2]  Eurocode 3: Design of steel structures - Part 1-1: General rules and rules for buildings; EN 1993-1-1:2010-12
[3]  National Annex - Nationally determined parameters - Eurocode 3: Design of steel structures - Part 1-1: General rules and rules for buildings; DIN EN 1993-1-1/NA:2015-08
[4]  Training Manual EC3. (2017). Leipzig: Dlubal Software.

更多信息

联系我们

联系 Dlubal

如果您有任何关于我们产品的问题或者建议,请联系我们的技术支持或者搜索我们的问题和解答 (FAQs)。

+49 9673 9203 0

(可要求接中文热线)

info@dlubal.com