7665x
001677
2020-07-06

Nonlinear Calculation of Floor Slab Made of Steel Fiber-Reinforced Concrete in Serviceability Limit State with RFEM

Describing the procedure for the serviceability limit state design of a floor slab made of steel fiber reinforced concrete. This article shows how to perform the corresponding design for the SLS by means of the iteratively determined FEA results.

The design of a floor slab made of steel fiber reinforced concrete consists of the ultimate limit state design and the serviceability limit state design. The procedure for performing the ultimate limit state design was explained in a previous Technical Article. The serviceability limit state design is now performed for the floor slab discussed in this previous article. This article shows how to perform the corresponding design for the SLS by means of the iteratively determined FEA results.

Entering Topology and Loads

The plate geometry and imposed loads are transferred from the ultimate limit state design (see the technical article mentioned above).

For the serviceability limit state design, the positive effects from shrinkage must also be taken into account. When shrinking, the floor slab wants to contract. Due to the interconnection or friction of the floor slab on the subsoil, tensile stresses occur which have to be considered. The base plate is embedded on the following layer structure (from top to bottom): Base plate, foil as a separating layer, perimeter insulation, bottom concrete layer, soil. According to [3], Table 4.19, a friction coefficient μ0 of 0.8 is recommended for this layer structure. For the design value μ0,d, the authors of [3] recommend a partial safety factor of γR = 1.25.

μ0,d = γR ⋅ μ0 = 1.25 ⋅ 0.8 = 1.0

In RFEM, the friction coefficient μ0,d can be defined as the nonlinearity of the surface elastic foundation. Image 02 shows the setting option in the program.

In the case of industrial floor slabs, the vertical load is of great importance for the formation of the positive action due to shrinkage strain. Before applying the rack loads and the stored goods, the self-weight of the floor slab is only available. As a result, the friction resistance of the bottom floor slab is relatively small. The tensile force Nctd resulting from the friction (referred to a 1-meter-wide strip) in the floor slab is determined as follows.

Nctd = μ0,d ⋅ σ0 ⋅ L/2
where
Nctd... the design value to determine the tensile stress in the floor slab when the friction force is reached,
μ0,d... the design value of friction,
σ0... Contact Pressure
L ... the length of the base plate for the displacement on the soil.

σ0 = 0.19 m ⋅ 1.0 m ⋅ 25 kN/m² = 4.35 kN/m² (self-weight of the slab)

Nctd = 1.0 ⋅ 4.75 kN/m² ⋅ 24.40 m/2 = 57.95 kN/m

The maximum resulting tensile stress σct,d resulting from friction thus results in
σct,d = Nctd / Act = 57.95 kN/m / 0.19 m = 305 kN/m² = 0.305 MN/m² <f fctm,fl = 2.9 MN/m².

The concrete tensile stress resulting from friction under the self-weight of the floor slab is smaller than the concrete tensile strength ffctm,fl. As a result, the shrinkage strain can be set free of cracks under the self-weight of the plate.

After applying the shelf loads/support reactions, however, due to the increased friction forces under the higher shelf supports, restraint forces occur that have to be considered in the calculation. In this project, the time of applying the shelf loads is assumed to be t = 180 days after concreting the floor slab. To calculate the shrinkage strain, ts = 7 days is used as the start of the shrinkage and t = 18,250 days as the end of use. Furthermore, a relative humidity of 50% is assumed. The shrinkage strain is applied as an external surface load by means of the axial strain load type. At this point, we would like to point out that you can use a help tool in the Surface Load dialog box that allows you to determine the shrinkage strain easily.

When applying the shrinkage strain, you must take into account that shrinkage does not cause any restraints in the plate up to the point of time t = 180 days. Therefore, only the positive shrinkage strain εcs,wk has to be applied for the design at time t = 18,250 days. This is calculated as the difference of the shrinkage strains at t = 18,250 and t = 180 days. A detailed calculation of the individual shrinkage strains is not described in this article.

εcs,wk = εcs (18,250, 7) - εcs (180, 7) = -0.515‰ - (-0.258‰) = 0.257‰

The positive shrinkage strain is defined as an additional load and taken into account in the load combinatorics for the time t = 18,250 days.

For the serviceability limit state design, the "Quasi-permanent" design situation is required. The variable load for storage spaces with the combination factor ψ2 = 0.8 is taken into account. These load combinations are used for the design of stresses as well as the limitation of crack widths caused by a load action.

In order to consider the imposed action from shrinkage at the end of use (t = 18,250 days), the previously created load combinations are copied and the "Shrinkage" load case is added to the positive shrinkage strain εcs,wk. These load combinations are used later for the crack width analysis under load action with restraint.

Define Material Properties for Serviceability Limit State Design

Use the "Isotropic Damage 2D/3D" material model of the RF-MAT NL add-on module to display the material behavior of steel fiber-reinforced concrete in RFEM. We use C30/37 L1.2/L0.9 concrete as steel fiber-reinforced concrete according to DIN EN 1992-1-1 [2] and the guideline by the German Committee for Reinforced Concrete (DAfStb) about steel fiber-reinforced concrete [1] with the two performance classes L1/L2 = L1.2/L0.9. For a nonlinear calculation, we apply the parabolic distribution according to 3.1.5 [2] on the compression side of the stress-strain diagram. Figure 05 shows the characteristic distribution of the working line of the aforementioned steel fiber-reinforced concrete.

We have to use the characteristic stress-strain curve for the serviceability limit state. As input help or help for the calculation of the diagram points, you can download an Excel file at the end of this technical article. You can transfer these diagram points to the RFEM input dialog box using the clipboard (see also the recommendations in the article about the ULS design).

Sserviceability Limit State Design

When performing the serviceability limit state design, you have to design the maximum allowable

  • limit stresses according to 7.2, DIN EN 1992-1-1 [2],
  • crack widths according to 7.3, DIN EN 1992-1-1 [2], and
  • deformations according to 7.4, DIN EN 1992-1-1 [2].

After successful nonlinear calculation of the base plate, the strains and stresses on the top and bottom sides are evaluated and used for the individual designs.

A) Design of Limit Stresses

The design of the maximum concrete compressive stress according to 7.2 (3) [2] is fulfilled if the maximum concrete compressive stress remains less than 0.45 ⋅ fck under quasi-permanent load action. For this purpose, the minimum stresses on the top and bottom sides are checked from the FEM calculation and compared to the limit value.

Top side:
maximum compressive stress σ2- = | - 8.5 | N/mm² <0.45 ⋅ fck = 13.5 N/mm²

Bottom side:
maximum compressive stress σ2+ = | - 3.1 | N/mm² <0.45 ⋅ fck = 13.5 N/mm²

Figure 06 shows the maximum compressive stress on the top side (-z) of the foundation plate.

Maintaining the maximum concrete compressive stress is successfully verified.

The design of the limitation of the maximum reinforcing steel stress according to 7.2. (4) and (5) [2] is not performed here because there is no reinforcing steel reinforcement.

B) Crack Width Analysis from Load Action

The crack width analysis is performed for the pure load action (at the point of time t = 180 days) and with additional consideration of the restraint due to shrinkage at the end of use (t = 18,250 days). See also the explanations above regarding shrinkage.

The existing crack width is determined on the basis of the quasi-permanent action combination. The existing crack width results from the integration of the governing strains over the crack bandwidth. The crack bandwidth is different for each load situation, and you have to take it manually from the results of the FEM calculation. The crack bandwidth is perpendicular to the considered strain direction and includes the strains that are greater than the crack strain εcr = 0.1‰.


where
εWk... Tensile strain within the crack band
dl... Differential of the crack bandwidth

To display the limits of the crack bands in RFEM, you can also control the color panel in a way so that only strains greater than the crack strain are displayed (see Figure 07).

For the evaluation of strains and crack bandwidth, we recommend creating a section for each considered crack band in RFEM. From this section, you can easily find the mean tensile strain and the crack bandwidth. The section must be defined parallel to the displayed strain direction. The crack width perpendicular to the x-axis on the bottom side governs in the analyzed slab. Figure 08 shows the created section with the average value for the tensile strains and the integration length.

The existing crack width wk,prov from pure load action (t = 180 days) results in
wk,prov,x = 0.219‰ ⋅ 1.172 m = 0.26 mm <0.3 mm (for exposition class XC 2).

C) Crack Width Analysis from Load Action and Effects Due to Restraint

The crack width analysis due to load action with restraint from shrinkage results at the end of the working life. When calculating the crack width using the strains from the FEM calculation, it is important to ensure that the strain causing stress is determined in a simple recalculation. This can be explained by the shrinkage behavior of the plate up to the time t = 180 days. If the plate can contract without constraint, the FEM calculation results in a distortion that is equal to the shrinkage strain. The resulting stress is equal to zero. A tensile stress only arises when a strain causing stress εwk, restraint occurs.

εwk,restraint = εFEM + | εcs,wk|
where
εwk,restraint... strain causing stress
εFEA... strain from FEM calculation
εcs,wk... Shrinkage strain

In order to determine the crack bandwidth in RFEM, it is necessary first to determine the strain of the finite element at which the element cracks under the applied restraint.

εcr,FEM,restraint = εcs,wk + εcr = -0.257‰ + 0.1 ‰ = -0.157‰

Figure 09 shows the governing section for the crack width calculation with load action and effects due to restraint. To integrate the strains across the crack bandwidth, the section must be divided into several areas.

The existing crack width is calculated as follows:

.

wk,prov,y = (-0.089‰ + 0.257‰) ⋅ 0.335 m + (0.059‰ + 0.257‰) ⋅ 0.450 m + (-0.093‰ + 0.257‰) ⋅ 0.402 m = 0.27 mm < 0.30 mm (for exposition class XC 2)

The crack width could be verified.

D) Deformation Analysis

The maximum deformations can be taken directly from the RFEM results. The total displacement under the quasi-permanent load is 32.8 mm. The deformation difference of the base plate results from the difference between the minimum and maximum deformations and amounts to 32.8 mm - 9 mm = 23.8 mm (see Figure 10).

The allowable limit values and the associated system compatibility for the rack must be agreed with the rack manufacturer.

Finally, we would like to point out the very helpful recommendations for performing nonlinear calculations with the "Isotropic Damage 2D/3D" material model in the technical article about the ultimate limit state design.


Author

Mr. Meierhofer is the development leader of programs for concrete structures and is available for the customer support team in case of questions related to reinforced and prestressed concrete design.

Links
References
  1. Stahlfaserbeton - Ergänzungen und Änderungen zu DIN EN 1992-1-1 in Verbindung mit DIN EN 1992-1-1/NA, DIN EN 206-1 in Verbindung mit DIN 1045-2 und DIN EN 13670 in Verbindung mit DIN 1045-3; DAfStb Stahlfaserbeton:2012-11
  2. Nationaler Anhang - National festgelegte Parameter - Eurocode 2: Bemessung und Konstruktion von Stahlbeton- und Spannbetontragwerken - Teil 1-1: Allgemeine Bemessungsregeln und Regeln für den Hochbau; DIN EN 1992-1-1/NA:2013-04
  3. Lohmeyer, G.; Ebeling, K.: Weiße Wannen - einfach und sicher, 11. Auflage. Erkrath: Bau+Technik, 2018
Downloads