291x
002062
2026-07-10

Reinforced Concrete Design of Isolated Footing Design According to ACI 318-19 (LRFD) in RFEM 6

This article demonstrates the design of a square isolated footing according to IBC (LRFD ) in RFEM 6. All relevant geotechnical checks are performed, including soil bearing pressure, sliding, overturning, uplift, and loads with large eccentricities. The governing LRFD load combinations are identified and verified step by step. The example is intended to provide a clear and practical reference for foundation design using the Concrete Foundations add-on.

Model Description (LRFD – Isolated Footing)

In this example, a simple square isolated footing is modeled.
A square reinforced concrete column is placed centrally on a square footing slab.
No stepped footing or special foundation geometry is used, in order to keep the example as simple as possible.

Geometry

  • Footing slab: 6.0 ft × 6.0 ft, thickness t = 1.75 ft
  • Column: 1.0 ft × 1.0 ft, height 2.0 ft, centrally positioned on the footing slab

Material Parameters

The following material parameter is used for the foundation design.

  • Concrete unit weight: γc = 150 lb/ft3 = 0.150 kip/ft3

Load Cases

Four load cases are defined in the model.

Load Case 1: Dead Load (Self Weight)

  • The self-weight of the model is automatically considered.
  • Additionally, a vertical force of 60 kip is applied at the top of the column in the +z-direction (acting downward).

Load Case 2: Live Load

  • A vertical force of 25 kip is applied at the top of the column in the +z-direction (acting downward).

Load Case 3: Wind Load (W+)

  • A member load of w = 2 kip/ft acting in the positive x-direction is applied to the upper half of the column (1 ft of the column height).
  • Additionally, a moment of -25 kipft about the y-axis is applied in the same rotational direction as the member load.

Load Case 4: Wind Load (W−)

  • A member load of w = 2 kip/ft acting in the negative x-direction is applied to the upper half of the column (1 ft of the column height).
  • Additionally, a moment of 25 kipft about the y-axis is applied in the same rotational direction as the member load.

Load Combinations (LRFD)

For the verification of the isolated footing, the load combinations according to the Load and Resistance Factor Design (LRFD) provisions of ASCE 7 | 2022, Section 2.3, are used.

The following load cases are defined in the model:
LC1 = D, LC2 = L, LC3 = W+, LC4 = W−

According to ASCE 7-22, Section 2.3, all basic combinations are first generated from the load cases present in the model. This complete set appears in RFEM under "Action Combinations". Combinations that are algebraically identical to a combination already covered under a different number are recognized as redundant and are not included in the actual calculation. Since no roof live load, snow load, rain load, or seismic action is defined in this model, Combinations 3 and 6 are not applicable.

The reduced set actually used for the calculation can be found under "Load Combinations." For this model, the following governing combinations result:

LRFD No. Load Combination RFEM Expression
1 1.40 · D 1.40 · LC1
2 1.20 · D + 1.60 · L 1.20 · LC1 + 1.60 · LC2
4 1.20 · D + 1.0 · L + 1.0 · W 1.20 · LC1 + 1.0 · LC2 + 1.0 · LC3
4 1.20 · D + 1.0 · L + 1.0 · W 1.20 · LC1 + 1.0 · LC2 + 1.0 · LC4
4 1.20 · D + 1.0 · W 1.20 · LC1 + 1.0 · LC3
4 1.20 · D + 1.0 · W 1.20 · LC1 + 1.0 · LC4
5 0.90 · D + 1.0 · W 0.90 · LC1 + 1.0 · LC3
5 0.90 · D + 1.0 · W 0.90 · LC1 + 1.0 · LC4
6 1.20 · D 1.20 · LC1
6 1.20 · D + 1.0 · L 1.20 · LC1 + 1.0 · LC2

To account for both possible wind directions, Combinations 4 and 5 each appear twice, once for W+ and once for W−.

All Load Combinations listed above are evaluated for the foundation design checks. For each verification (flexural design, one-way shear, two-way shear), the governing load combination with the highest utilization ratio is determined.

Determination of Vertical Dead Load (Load Case 1)

Load Case 1 contains the total vertical dead load acting on the foundation.
This includes the applied column load, the self-weight of the footing and column, and the weight of the soil cover above the footing.

Self-weight of footing

Wf = 6.0 ft · 6.0 ft · 1.75 ft · 0.150 kip/ft3 = 9.45 kip

Self-weight of column

Wc = 1.0 ft · 1.0 ft · 2.0 ft · 0.150 kip/ft3 = 0.30 kip

Weight of soil cover

Gsoil = (6.0 ft · 6.0 ft − 1.0 ft · 1.0 ft) · 1.0 ft · 0.110 kip/ft3 = 3.85 kip

Total vertical load in Load Case 1

PLC1 = 60.0 kip + 9.45 kip + 0.30 kip + 3.85 kip = 73.60 kip

Concrete Design Checks

The isolated footing is verified according to the LRFD approach defined in IBC/ACI 318-19.
RFEM automatically evaluates all relevant load combinations and determines the governing combination for each design check.

Flexural Design (Bottom Reinforcement)

For this example, the governing load combination for the bottom reinforcement in x-direction is LRFD Combination 4 (1.20D + 1.0L + 1.0W+), and for the bottom reinforcement in y-direction it is LRFD Combination 2 (1.20D + 1.60L).
According to ACI 318-19 §13.2.6.4, the factored moment for the bottom longitudinal reinforcement results from the superposition of the moment from the compressive stress block (soil bearing pressure) and the moment from additional foundation loads, as shown in the design section at the column face.

Bottom Reinforcement, x-Direction

Mf,x,(bottom),u = max(MC,+x,(bottom) + MA,+x,(bottom) ; MC,−x,(bottom) + MA,−x,(bottom) ; 0) / Φ
= max(70.87 kipft − 8.38 kipft ; 47.17 kipft − 8.38 kipft ; 0) / 0.900 = 69.43 kipft
M2w,u = √((0.60 · −28.00 kipft)² + (0.60 · 0.00 kipft)²) / 0.900 = 18.67 kipft
Mf,x,(bottom),u = max(69.43 kipft ; 18.67 kipft) = 69.43 kipft
As,stat,x,(bottom) = max(0.72 in² ; 0.00 in²) = 0.72 in²

Utilization ratio

η = As,stat,x,(bottom) / As,prov,x,(bottom) = 0.72 in² / 3.16 in² = 0.227 [-]
Since η < 1.0, the flexural check for the bottom reinforcement in the x-direction is satisfied.

Bottom Reinforcement, y-Direction

Mf,y,(bottom),u = max(66.83 kipft − 8.38 kipft ; 66.83 kipft − 8.38 kipft ; 0) / 0.900 = 64.94 kipft
Since LRFD Combination 2 contains no wind action, there is no moment transfer at the critical punching shear perimeter: M2w,u = 0.00 kipft
My,(bottom),u = max(64.94 kipft ; 0.00 kipft) = 64.94 kipft
As,stat,y,(bottom) = max(0.69 in² ; 0.00 in²) = 0.69 in²

Utilization ratio

η = As,stat,y,(bottom) / As,prov,y,(bottom) = 0.69 in² / 3.16 in² = 0.220 [-]
Since η < 1.0, the flexural check for the bottom reinforcement in y-direction is satisfied.

Top Reinforcement (x- and y-Direction)

For this example, the top reinforcement utilization ratios are η = 0.000 in both directions.
The governing combinations produce compression-controlled sections (Φcompr = 0.65) with a resulting factored top moment of 0 kipft.

One-Way Shear

The one-way shear strength is verified according to ACI 318-19 §22.5 at the critical section located at a distance d from the column face.
For this example, the governing load combination is LRFD Combination 2 (1.20D + 1.60L).

Applied Shear Force

Vu = max(0 ; VC,red+ − VA,red+ ; VC,red− − VA,red−) = max(0 ; 19.815 kip − 2.485 kip ; 19.815 kip − 2.485 kip) = 17.330 kip

Shear Resistance

Vc = Vc(c) = min(5 · λ · √f'c · bw · d, (8 · λs · λ · (ρw)1/3 · √f'c + min(0.05 · f'c, Nu / (6 · Ag))) · bw · d)
= min(5 · 1 · 63.2 psi · 72 in · 18.881 in, (8 · 1 · 1 · (0.23 %)1/3 · 63.2 psi + min(0.05 · 576 ksf, 0)) · 72.000 in · 18.881 in)
= 91.093 kip
Vmax = ΦV,T · (Vc + 8 · √f'c · bw · d) = 0.750 · (91.093 kip + 8 · 63.2 psi · 72.000 in · 18.881 in) = 584.310 kip

Utilization ratio

η = max(Vu / (ΦV,T · Vn) ; Vu / Vmax) = max(17.330 kip / (0.750 · 91.093 kip) ; 17.330 kip / 584.310 kip) = 0.254 [-]
Since η < 1.0, the one-way shear check is satisfied for LRFD Combination 2.

Two-Way (Punching) Shear

The punching shear strength is verified according to ACI 318-19 §22.6 at the critical perimeter located at d/2 from the column face.
For this example, the governing load combination is LRFD Combination 4 (1.20D + 1.0L + 1.0W+).

Applied Shear Stress

vu = vuv − (γv,1 · Msc,1,sl · e₁ / J₁) + (γv,2 · Msc,2,sl · e₂ / J₂) = 4.748 ksf − (0.40 · −28.00 kipft · 15.597 in / 388401 in⁴) + (0.40 · 0.00 kipft · −15.597 in / 388401 in⁴) = 5.526 ksf

Shear Resistance

vc = min(vc,(a) ; vc,(b) ; vc,(c)) = min(36.429 ksf ; 54.644 ksf ; 74.253 ksf) = 36.429 ksf

Utilization ratio

η = |vu| / (ΦV,T · vn) = |5.526 ksf| / (0.750 · 36.429 ksf) = 0.202 [-]
Since η < 1.0, the two-way (punching) shear check is satisfied for LRFD Combination 4.

Minimum Reinforcement

In addition to the flexural design checks above, the minimum longitudinal reinforcement area for the bottom reinforcement is verified for both the x- and y-direction according to ACI 318-19. The required reinforcement area results from the greater of the statically required reinforcement and the minimum reinforcement area specified by the code.

Minimum Reinforcement, x-Direction

As,stat,x,(bottom) = max(As,stat,t,x,(bottom) ; As,stat,p,x,(bottom)) = max(0.50 in² ; 0.00 in²) = 0.50 in²
Mf,x,(bottom),u = max(MC,+x,(bottom) + MA,+x,(bottom) ; MC,−x,(bottom) + MA,−x,(bottom) ; 0) / Φ
= max(53.66 kipft − 9.78 kipft ; 53.66 kipft − 9.78 kipft ; 0) / 0.900 = 48.76 kipft
As,req,x,(bottom) = max(As,stat,x,(bottom) ; As,min,x,(bottom)) = 2.72 in²

Utilization ratio

η = As,req,x,(bottom) / As,prov,x,(bottom) = 2.72 in² / 3.16 in² = 0.862 [-]
Since η < 1.0, the minimum reinforcement check for the bottom reinforcement in the x-direction is satisfied.

Minimum Reinforcement, y-Direction

As,stat,y,(bottom) = max(As,stat,t,y,(bottom) ; As,stat,p,y,(bottom)) = max(0.52 in² ; 0.00 in²) = 0.52 in²
Mf,y,(bottom),u = max(MC,+y,(bottom) + MA,+y,(bottom) ; MC,−y,(bottom) + MA,−y,(bottom) ; 0) / Φ
= max(53.66 kipft − 9.78 kipft ; 53.66 kipft − 9.78 kipft ; 0) / 0.900 = 48.76 kipft
As,req,y,(bottom) = max(As,stat,y,(bottom) ; As,min,y,(bottom)) = 2.72 in²

Utilization ratio

η = As,req,y,(bottom) / As,prov,y,(bottom) = 2.72 in² / 3.16 in² = 0.862 [-]
Since η < 1.0, the minimum reinforcement check for the bottom reinforcement in the y-direction is satisfied.

Conclusion

This example demonstrates the complete structural design workflow for an isolated footing in RFEM according to ACI 318-19, using LRFD load combinations according to ASCE 7. The workflow includes all relevant reinforced concrete design checks, including flexural design of the bottom and top reinforcement, one-way shear, and two-way (punching) shear.

The evaluation shows that all governing verification criteria are satisfied. The provided reinforcement is sufficient in both principal directions, while the shear and punching shear checks confirm adequate structural capacity without requiring shear reinforcement.

Overall, this example illustrates how RFEM provides a transparent and efficient workflow for reinforced concrete footing design, enabling engineers to evaluate design moments, shear forces, reinforcement requirements, and governing load combinations in a single design process.


Author

Ann-Kathrin works in Product Engineering, focusing on geotechnical engineering, and also assists with customer support.



;